Firmware V3.13
21.04.2021
110/466
•
•
•
•
•
•
5.16 Refrigeration point disabling
The case controller enables refrigeration points to be disabled by the pack controller (e.g. VS 3010) via the
CAN bus. Cooling by the case controller is interrupted as long as refrigeration point disabling is active.
5.17 E*COP+
The auto-adaptive E*COP+ control process dynamically adjusts the suction pressure to the current cooling
power requirement. The algorithm evaluates the operating data of all controllers and determines the optimum
suction pressure over the respective requesting cooling units. The suction gas pressure p
0
and evaporation
temperature t
0
are dynamically increased as much as possible. The process uses the fact that less
compression work has to be performed in the case of an increase of p
0
and t
0
. Depending on the operating
status, increasing the evaporation temperature by 1 K can save approx. 3% energy. In the case of fluctuating
partial loads, E*COP+ always finds the ideal operating point and improves the COP (Coefficient of
Performance).
Parameters for E*COP+
This is the standard operating mode for suction pressure shifting. The operating mode is also suitable for mixed
operation of EEV and TEV controllers. Since all controllers participate in the suction pressure shift, all of them
(including the TEV controllers)
must also
be set to COPT+. In order for the EEV refrigeration controller (from
version >= V1.90) to be included in the control procedure, the following parameters must be set:
Menu 6-1: Refr. Sys. No.
Menu 6-2-7: OD over CAN set to
OFF
Menu 6-2: COPT+ set to
ON
Parameters for E*COP+ (compatibility mode with existing systems)
This operating mode serves to maintain compatibility with existing systems with UA 400 E / UA 410 E
controllers up to version V1.89. As soon as
one
of the controllers participating in E*COP+ uses this "older"
mode, all other controllers must also be set to this mode. Mixed operation of EEV/ TEV is then
no
longer
possible! In order for the EEV refrigeration controller to be included in the control procedure in compatibility
mode, the following parameters must be set:
Menu 6-1: Refr. Sys. No.
Menu 6-2-7: OD over CAN set to
ON
Menu 6-2: COPT+ set to
OFF
5.18 Suction pressure shift
Current valve opening degrees and case/superheat control status is transmitted by the case controller to the
pack controller via the CAN bus to enable suction pressure setpoint shift to be made on the pack controller
according to the actual refrigeration load. Transmission of the case controller valve opening degrees to the
pack controller can be switched on and off by the VO via CAN parameter (menu 6-2-7). (This can only be done
in Superuser mode). Thus it is possible for transmission of these positions to be disabled individually on any
case controller that is not to be included in suction pressure shift. The suction pressure setpoint on the pack
controller is shifted up or down according to the opening degree of the case/coldroom controllers concerned.
The action can be defined on the pack controller. Suction pressure setpoint is
not
shifted up when one of the
controllers concerned switches to superheat control and when temperature on the room/return air sensor is
greater than the room/return air se 2K. The suction pressure setpoint is accordingly not shifted up only
when a display case is at ”warm” temperature and has also switched to superheat control.
A detailed description of the required settings and parameters can be found online on our
https://edp.eckelmann.de/edp/lds/_AzMqeNOO3W
.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...