Firmware V3.13
21.04.2021
280/466
•
•
Menu 2-1-1 Zone 1
COOLING 1 POS: XXXXX
Entry
Default
Setpoint R2.1 XXX °C
Supply air temperature setpoint
--, -20..20
-4 °C
Hystersis R2.1 X K
Supply air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-1)
1..8
2 K
Setpoint R4.1 XXX °C
Return air temperature setpoint
--, -15..20
2 °C
Hystersis R4.1 X K
Return air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-1)
1..8
2 K
Superheat XXX K
Superheat setpoint Zone 1
0..20
6 K
Min. SH XX K
Minimum superheat setpoint, below which cooling relay
switches off in Zone 1. I-sum (not I-part) is set to zero
when the
Reset I-Sum
parameter is set to ON.
0..10
2 K
Two pos.ctrl XXX
Switch between on-off control (ON) and continuous
control (OFF)
↑, ↓
(ON/OFF)
OFF
MOP-point XXX °C
Starting setpoint for MOP mode
--, -50..50
– °C
Cool. on AOUT XXX%
Kühlung eingeschaltet: fester Wert 0..10 V für
Analogausgang AO1; nur sichtbar, wenn von DIP-
Schalter S3 der Kodierschalter 6 auf ON steht, siehe
Kapitel
Funktionsweise der Analogausgänge 0..10 V.
0..100
80 %
Cool. off AOUT XXX%
Kühlung ausgeschaltet: fester Wert 0..10 V für
Analogausgang AO1; nur sichtbar, wenn von DIP-
Schalter S3 der Kodierschalter 6 auf ON steht, siehe
Kapitel
Funktionsweise der Analogausgänge 0..10 V.
0..100
50 %
Menu 2-1-2 Zone 2
COOLING 2 POS: XXXXX
Entry
Default
Setpoint R2.2 XXX °C
Supply air temperature setpoint
--, -20..20
4 °C
Hystersis R2.2 X K
Supply air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-2)
1..8
4 K
Setpoint R4.2 XXX °C
Return air temperature setpoint
--, -15..20
2 °C
Hystersis R4.2 X K
Return air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-2)
1..8
2 K
Superheat XXX K
Superheat setpoint Zone 2
0..20
6 K
Min. SH XX K
Minimum superheat setpoint, below which cooling
relay switches off in Zone 2. I-sum (not I-part) is set to
zero when the Reset I-Sum parameter is set to ON.
0..10
2 K
Two pos.ctrl XXX
Switch between on-off control (ON) and continuous
control (OFF)
↑, ↓ (ON/OFF)
OFF
MOP-point XXX °C
Starting setpoint for MOP mode
--, -50..50
-- °C
Cool. on AOUT XXX%
Kühlung eingeschaltet: fester Wert 0..10 V für
Analogausgang AO2; nur sichtbar, wenn von DIP-
Schalter S3 der Kodierschalter 6 auf ON steht, siehe
Kapitel
Funktionsweise der Analogausgänge 0..10 V.
0..100
80 %
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...