Firmware V3.13
21.04.2021
315/466
•
•
9.4.3 Menu 2 Setpoints UR 141 NE
SETPOINTSPOS: XXXXX
1 Cooling
Move to menu 2-1;
Special case:
When one-zone (tandem) operation is set (Menu 6-1) and setpoint
toggle is deactivated (Menu 3-3), Continue to 2-1-1
2 Defrost
Move to menu 2-2;
Special case:
When one-zone (tandem) operation is set (Menu 6-1) and setpoint
toggle is deactivated (Menu 3-3), Continue to 2-2-1
3 Fans
Move to menu 2-3;
Special case:
When one-zone (tandem) operation is set (Menu 6-1) and setpoint
toggle is deactivated (Menu 3-3), Continue to 2-3-1
4 Alarm
Move to menu 2-4;
Special case:
When one-zone (tandem) operation is set (Menu 6-1) and setpoint
toggle is deactivated (Menu 3-3), Continue to 2-4-1
5 Frame Heater
Move to menu 2-5
Menu 2-1 Cooling
COOLINGPOS: XXXXX
1 Zone 1
Move to menu 2-1-1
2 Zone 2
Move to menu 2-1-2; shown only when two-zone operation is set (Menu 6-1)
3 Zone 1T Toggle
Move to menu 2-1-3; not shown when setpoint toggle is deactivated (Menu 3-3)
3 Zone 2T Toggle
Move to menu 2-1-4; shown only when two-zone operation is set (Menu 6-1) and when
setpoint toggle is not deactivated (Menu 3-3)
Menu 2-1-1 Zone 1
COOLING 1POS: XXXXX
Entry
Default
Setpoint R4.1 XXX °C
Room air temperature setpoint
--, -10..30
5 °C
Hystersis R4.1 X K
Room air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-1)
1..8
2 K
Ht. Cir. Setp.
Heating circuit control setpoint; shown only when
single-zone is set (Menu 6-1)
--, -10..30
5 °C
Ht. Cir. Hyst.
Heating circuit control hysteresis setpoint;; shown only
when single-zone is set (Menu 6-1)
1..8
2 K
Superheat XXX K
Superheat setpoint Zone 1
0..20
6 K
Min. SH XX K
Minimum superheat setpoint, below which cooling
relay switches off in Zone 1. I-sum (not I-part) is set to
zero when the
Reset I-Sum
parameter is set to ON.
0..10
2 K
Two pos.ctrl XXX
Switch between on-off control (ON) and continuous
control (OFF)
↑, ↓, (ON/OFF)
OFF
MOP-point XXX °C
Starting setpoint for MOP mode
--, -50..50
– °C
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...