Firmware V3.13
21.04.2021
383/466
•
Menu 6-5 Alarm priorities
ALARMPRIOS POS: XXXXX
Entry
Default
Prio.Refrig. Pt. X
Global setting of alarm priority via refrigaration point
priority (Menu 6-1) (Y)
↑, ↓,
(Y/N)
N
Priority: XX
Displays refrigeration point priority (Menu 6-1); only
shown when refrigeration point priority is set to Y
Following parameters are only shown when refrigeration point priority is set to N. Meaning of valid entries for alarm priority is as follows:
- = Event ignored
0 = Message (enterd only in message log)
1 = Priority 1 alarm
..
99 = Priority 99 alarm
Low Temp.
Temperature below low alarm limit.
Priority applies to alarms
Low Temp. Zone 1, Low
Temp. Zone 2
-, 0..99
2
High Temp.
Temperature above high alarm limit.
Priority applies to alarms
High Temp. Zone 1, High
Temp. Zone 2
-, 0..99
1
Sensor Fault
Temperature sensor failure
-, 0..99
2
Door Open
Coldroom door open longer than time delay; pririty
applies to
Coldroom Door Open
alarm
-, 0..99
2
No Defrost
No defrost within alarm delay time. Priority applies to
No
Defrost
alarm
-, 0..99
0
Timer-Term. Defrost
Defrosting terminated by safe defrost time
-, 0..99
0
Power Failure
Start following power failure
-, 0..99
0
First Start
Controller Startup (basic settings are loaded!)
-, 0..99
2
Manual Shutoff
Manual switch Input D31/D32 set OFF
-, 0..99
0
Hardware Fault
Internal hardware defect. Priority applies to alarms
EEPROM Defective, RTC Defective, Flash Memory
Defective
-, 0..99
1
Setpoint Change
Message generated when changing setpoints
0..99
0
Refrig.Pt.Dis.
Cooling interrupted by VS pack controller via CAN bus
-, 0..99
0
Battery Voltage
Battery low
-, 0..99
0
Check t0
The pack controller to is not received via CAN bus;
priority is given to the messages Check to Z1, Check to
Z2 (see also chapter
-, 0..99
2
Sensor Fault eev
EEV Control sensor failure. Priority applies to alarms
Sensor Break EEV Z1, Sensor Break EEV Z2
-, 0..99
2
eev ctrl block
EEV control stalled. Priority applies to alarms
EEV Stall
Detect Z1, EEV Stall Detect Z2
-, 0..99
0
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...