Firmware V3.13
21.04.2021
142/466
7.
8.
9.
Restore power to the case controller and refrigeration point. Refrigeration point operates again.
Controller in the CAN bus system
: With unchanged configuration of the system centre / store computer,
the controller is automatically detected again via the CAN bus; date, time and automatic summer / winter
time changeover are set automatically via the central time synchronisation.
Controller in standalone operation
: The setting of date, time and automatic summer / winter time
changeover is required for the data archiving (Menu 3-1).
In the case of
Restart - restart of the controller
, (error) messages are output. These must be checked /
acknowledged in the higher level controller or using the set-up unit!
DANGER
Warning about dangerous electrical voltage! Danger of electric shock!
A voltage of 230 V AC
can be present on some connectors.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...