Firmware V3.13
21.04.2021
35/466
Explanation for the sensor designation
Legend: Ry.x
y = type of the sensor
1
2
4
5
6
Defrost sensor
Supply air sensor
Return air sensor / room air sensor / refrigerant temperature sensor
(UK 100 E)
Evaporator inlet sensor
Evaporator outlet sensor
x = case
1/2
Zone 1 / Zone 2
Error message in the event of sensor fault
An alarm (sensor fault) is always triggered if necessary sensors are not attached. If optional sensors are not
attached, this alarm only occurs if these sensors have been incorporated in a sensor scan. A sensor scan is
started via menu 6-1 (see chapter
).
5.6 Description of controller functions
The sections that follow describes the various functions of the case controller for control of refrigeration
points equipped with an electronic expansion valve. The availability of certain controller functions is governed
by which controller type is set on DIP Switch S3 (see Section
Setting the controller type and other functions
).
ATTENTION
The evaporator inlet sensors R5.1 and R5.2 are
optional,
if the case controller on the CAN bus is
operated with a pack controller. In
standalone operation
using evaporator inlet sensors, R5.1 and
R5.2 are
necessary
sensors, see chapter
Standalone operation using evaporator inlet sensors
! These
must be connected and integrated using sensor scan to prevent any error message! In the case of
optional sensors that are not included in a sensor scan, no actual values are archived in the system
centre / store computer.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...