Firmware V3.13
21.04.2021
203/466
•
•
•
•
•
Menu 2-4 Alarm
ALARM POS: XXXXX
1 Zone 1
Move to menu 2-4-1
2 Zone 2
Move to menu 2-4-2; shown only when two-zone operation is set (Menu 6-1)
3 Zone 1T Toggle
Move to menu 2-4-3; not shown when setpoint toggle is deactivated (Menu 3-3)
4 Zone 2T Toggle
Move to menu 2-4-4; shown only when two-zone operation is set (Menu 6-1) and when
setpoint toggle is not deactivated (Menu 3-3)
Menu 2-4-1 Zone 1
ALARM 1 POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
0..30
8 °C
Low Temp Setp. XX K
Temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
4 K
Menu 2-4-2 Zone 2
ALARM 2 POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
0..30
8 °C
Low Temp Setp. XX K
Temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
4 K
Menu 2-4-3 Zone 1T Toggle
ALARM 1A POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
0..30
8 °C
Low Temp Setp. XX K
Temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
4 K
Menu 2-4-4 Zone 2T Toggle
ALARM 2A POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
0..30
8 °C
Low Temp Setp. XX K
Temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
4 K
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...