Firmware V3.13
21.04.2021
379/466
•
Menu 6-2-7 EEV Controller Zone 1
EEV ZONE 1 POS: XXXXX
Entry
Default
Pc Z 1: XX.XX
Temperature control Zone 1, P-part
0..99.99
7.00
Ic Z 1: XX.XX
Temperature control Zone 1, I-part
If parameter I
c
is reduced, internal learned value
(sum of I-part) is deleted and re-learned in due
course.
0..99.99
0.30
Dc Z 1: XX.XX
Temperature control Zone 1, D-part
0..99.99
5.00
offs OD cab. XX %
Percentage valve opening degree offset for
temperature control
If offset is changed, internal learned value (sum of
I-part) is deleted and re-learned in due course.
0..100
30 %
Psh Z 1: XX.XX
Superheat control Zone 1, P-part
0..99.99
5.00
Ish Z 1: XX.XX
Superheat control Zone 1, I-part
If parameter I
sh
is reduced, internal learned value
(sum of I-part) is deleted and re-learned in due
course.
0..99.99
0.10
Dsh Z 1: XX.XX
Superheat control Zone 1, D-part
0..99.99
5.00
offs OD SH XX %
Percentage valve opening degree offset for
superheat control
If offset is changed, internal learned value (sum of
I-part) is deleted and re-learned in due course.
0..100
10 %
emerg.c-o OD XX %
Maximum emergency valve opening degree
0..50
20 %
delay min SH XX s
Delay on drop of superheat below set minimum
9..600
9 sec
setuptime XX.X m
Setup time following the switching on of the
controller or following a defrost or in the event of
a blockade of the regulation.
The value entered must not be less than the
current ”
inject.time
” parameter, otherwise the
smallest valid value will be used.
Further details about “Fixed valve opening degree
in pumpdown/feed-in phase” see chapter
valve opening degree in pumpdown/feed-in
phase
.
0..100.0
2.0 min
•
•
This menu is only visible if
the “Master” mode is activated in the system centre, i.e.
the “Superuser mode” is activated in the store computer.
chapter.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...