Firmware V3.13
21.04.2021
83/466
defrost in the following consecutive defrost group is delayed accordingly.
The defrosts are continued until the entire chain of controllers has been run through. This completes the
consecutive defrost and all controllers are back in cooling mode. >
Configuration / oarametrisation of consecutive defrost
The parametrisation of the defrost is performed in menu 2 - Setpoints – 2 Defrost Zone 1.
The first thing to be configured is the function of the controller with regard to the consecutive defrost (Master or
Slave or OFF if the controller does not participate in the consecutive defrost, parameter "
FA-Funktion
").
The associated defrost group (parameter
FA-Gruppe
) and the CAN bus address of the CD Master
(parameter
FA-Master
) must be set for the slaves. The CD master is automatically in CD group 1; if it is set to a
different group, this has no effect on the master. Furthermore, the wait time between two group defrosts must
be set on the CD master.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...