Performing the battery replacement
Disconnect case controller and refrigeration point from the power supply. Acknowledge alarm in the higher
level controller if necessary.
Disconnect all plug connectors, remove the device from the DIN rail.
(A)
Push the plastic lid’s two left-hand snap lugs on the side upwards with a broad flat blade screwdriver
and
(B)
lift up the lid with a swivelling movement.
(C)
Pull the battery (C) upwards out of the battery holder and dispose of it correctly.
Pick up the new battery with a cloth and press it into the battery holder.
Check that the lid is in the correct position and push it down until it clicks into place.
Put device on the DIN rail and attach all connectors again.
DANGER
Warning about dangerous electrical voltage! Danger of electric shock!
A voltage of 230 V AC
can be present on some connectors.
ATTENTION
The device contains a lithium battery (for
details, see chapter
disposed of separately!
Never dispose of this product with other
domestic waste. Please inform yourself about
the local regulations for the separated disposal
of electrical and electronic products and
batteries. The correct disposal of your old
equipment protects the environment and people
against possible negative consequences.
correctly
•
•
•
ATTENTION
Do
not
handle the new battery with metal pliers as the battery can be destroyed by the resulting
short circuit:
wipe with a clean and dry cloth.
do
not
hold on the edge contact areas,
observing polarity.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...