• Menü 2-2-1 Zone 1
DEFROST 1 POS: XXXXX
Entry
Default
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 5..20
8 °C
Wait Time XX m
Waiting time setpoint between cooling and defrost
0..15
0 min
Drip Time X m
Waiting time (drip time) setpoint between defrost and
cooling
0..15
0 min
M/S Degiv.Fct. XXX
Configuration of the defrost via CAN bus function. For
details see chapter
.
OFF,
MASTR, SLAVE
OFF
M/S CAN Adr. XXX
Selection of the controller (1..99) participating in the
defrost via CAN bus which is the master. “--“, if this
controller is itself master (Parameter M/S Degiv.Fct.. =
MASTR)
---, 1..99
–
DS-Function XXX
Configuration of the defrost sequenz function (DS). For
details see chapter
Defrost sequenz (DS) via CAN bus
.
OFF,
MASTR,
SLAVE
OFF,
DS-Group XXX
Selection of which group a defrost sequenz of this
controller (1..99) belongs to
---, 1..99
–
DS-Master XXX
Selection of which controller (1..99) participating in the
defrost sequenz is the master. “--“, if this controller is
itself the master (Parameter DS-Function = MASTR)
---, 1..99
–
DS-Wait time XXXm
Wartezeit der Folgeabtauung
0..127
1 min
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...