Firmware V3.13
21.04.2021
54/466
•
•
•
•
5.7.8 Connection of pressure transmitters / humidity sensors
Only UA 410 E AC
In order to measure the suction pressure at the case controller, a low pressure transmitter 0..10 bar can be
connected. The electrical connection of the pressure transmitter, i.e. humidity sensor, is carried out according to
the same principles as those familiar from the pack controller. The parametrisation and functionality of the two
analogue inputs AIN1/AIN2 (terminals 11/12 and 11/14) are performed using the menu 6-2-6. The actual value
is acquired via 4..20 mA. For further details, see chapter
Belegung der 4..20 mA-Analogeingänge
The following setting options are provided:
Activation of the analogue input (whether it is used at all). For further details, see chapter
Selection of the used refrigerant (can be set for each sensor):
*Supported refrigerants: R404A, R744 (CO2), R134a, R410A, R717 (NH3), R22, R290, R407C, R507,
R1270, R402A, R502, R407F, R422A, R422D, R408A, R407D, R407A, R427A, R438A, R152a, R170,
R600, R600a, R449A, R450A, R448A, R455A, R447B, R1234ze, R1233zd, R1234yf, R513A
Adjustment of the analogue input to the pressure transmitter employed: Input of the lowest/highest pressure
values (factory side 0..10 bar)
Type of measurement:
Analogue input 1 (AIN1): t
0
(fixed setting, cannot be parametrised)
Analogue input 2 (AIN2): selection between t
0
, humidity, t
c
or t
c
LT
If the transcritical range is exceeded during the measurement of t
c
with the refrigerant R744 (CO
2
), the
temperature continues to be converted; however it no longer corresponds to the pressure. There is no
built-in limitation at 31 °C in this version. Currently, the pressure in respect of t
0
/t
c
is neither measured
nor displayed, only the temperatures.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...