Firmware V3.13
21.04.2021
285/466
•
•
•
•
•
Menu 2-4-2 Zone 2
ALARM 2 POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which High
Temperature alarm is generated
-10..30
6 °C
Low Temp Setp. XX K
Temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
4 K
Menu 2-4-3 Zone 1T Toggle
ALARM 1A POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which
High
Temperature
alarm is generated
-10..30
6 °C
Low Temp Setp. XX K
Temperature setpoint (difference below
temperature control setpoint) at which
Low
Temperature
alarm is generated
--, 0..6
4 K
Menu 2-4-4 Zone 2T Toggle
ALARM 2U POS: XXXXX
Entry
Default
High Temp Setp XX °C
High temperature setpoint at which High Temperature
alarm is generated
-10..30
6 °C
Low Temp Setp. XX K
Temperature setpoint (difference below temperature
control setpoint) at which Low Temperature alarm is
generated
--, 0..6
4 K
Menu 2-5 Not used with this controller type.
Menu 2-6 Pane Heater
PANE HTR POS: XXXXX
1 Mode pane
Move to menu 2-6-1
2 Setpoint Pane
Move to menu 2-6-2
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...