Firmware V3.13
21.04.2021
453/466
•
•
126
Timer-Term. Defrost
The defrost has been ended via the safe
defrost time.
Heater defective, contactor defective,
evaporator iced up.
Check parametrisation: Defrost termination
temperature too low, check evaporator for
icing up, check position of the defrost
sensor, set defrost termination temperature
to "−−".
127
Manual shutdown
Digital input
manual shutdown
has been set
–
No.
Message text
Cause
Remedy
Messages
128
Sensor Fault (Fx)
A sensor has been removed, a short-circuit
or interference has occurred at the sensor.
The temperature at the sensor is outside the
specified measuring range.
Check connection cable, check shield or replace
affected sensor. F1..F9 = terminal Z11/
Z12..Z91/92F10 = terminal Z01/Z02
Sensor fault A1, A2
The message “Sensor fault A1/A2” is
displayed if the parameter “AIN1” and/or
“AIN2” of the analogue inputs in menu 6-2-6
are set to “Active=Yes” but no sensor is
detected. Note: A1/A2 = analogue input
AIN1/AIN2
Check connection cable, check shield, replace
affected sensors or set parameters "AIN1" and/or
"AIN2" in menu 6-2-6 to "AIN1/2 active=no"
131
Check OD
A controller state has been reached which
generates implausible values for the opening
degree (see chapter
Check refrigeration point / controller with regard to
electrical connection of the cooling relay
correct mechanical closing and opening of
the liquid solenoid valve
Possibly, check control sensors for wiring
errors.
138
Check t
0
: Zone1
The pack controller t
o
has not been received
via CAN bus; priority is given to the
messages "check Z1 to", "check Z2 to"
Check pack number of the case controller, check
setting of the parameter
Korroff. to
, check CAN
bus. See also chapter
Check t
0
: Zone2
139
Sensor Fault EEV Z1
Sensor fault on the necessary control
sensors for the EEV regulation.
Replace affected sensors
Sensor Fault EEV Z2
140
eev ctrl block Z1
The
regulation blocked
state has occurred 3
times in succession and has not been
rectified independently by the controller.
Check control sensors for correct position. When
operating the superheat control with two
temperature sensors without t0 via the CAN bus,
this error message can occur during operation
without an error being present. The alarm can then
be removed from the alarm signalling with a
priority of 0.
eev ctrl block Z2
141
Wrong controller type
Unsupported controller type set at the DIP
switch
Change controller type (see chapter
controller type and other functions
)
142
emerg.cut-out SH Z1
The E-valve has been closed because the
emergency superheat has been undercut for
longer than the parametrised delay time.
Check superheat control sensors for correct
position.
emerg.cut-out SH Z2
ATTENTION
In the case of controllers with off-
cycle defrosting, it can occur that
the defrost is ended via the safe
defrost time. Therefore, the
message can be displayed
cyclically for these controllers
without an error having occurred.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...