Firmware V3.13
21.04.2021
452/466
•
•
•
11 Alarms and messages UA 4xx E
The table contains all message texts and their possible cause. Each message text has a priority that can be
set in the
Alarm Priorities
screen (menu 6-5).
No.
Message text
Cause
Remedy
Hardware error
4
EEPROM error
A chip for saving the configuration is
defective or the configuration data in the
EEPROM are not plausible.
Save parameters using the LDSWin
software, possibly initiate first start and
restore parameters using LDSWin. Please
contact Customer Service if the error still
occurs
6
Flash Fault
The flash memory module is defective.
Please contact Customer Service - replace
device
8
RTC error
The real-time clock is defective.
Please contact Customer Service - replace
device
10
Battery Voltage
The battery for the real-time clock and RAM
backup is discharged.
Messages
50
First Start
The case controller has performed a first
start (loading of the default settings / sensor
scan)
–
51
Power Failure
Restart of the controller after a power
failure.
Check 230 V power supply
120
Low temp. zone 1
Lower limit value at the monitored control
sensors in Zone 1 undercut
Check parametrisation, sensors,
installation
121
Low temp. zone 2
Lower limit value at the monitored control
sensors in Zone 2 undercut
Check parametrisation, sensors,
installation
122
High temp. zone 1
Upper limit value at the monitored control
sensors in Zone 1 exceeded
Check parametrisation, sensors,
installation
123
High temp. zone 2
Upper limit value at the monitored control
sensors in Zone 2 exceeded
Check parametrisation, sensors,
installation
124
Cold room door open
Cold room door Z1/Z2
The cold room door or cold room door Z1 or
Z2 is opened beyond the alarm time; only
for cold room controllers.
Close door, check door switch or
connection cable
125
No Defrost
No defrost within the alarm time.
A consecutive defrost via CAN bus
has not been configured correctly
A master/slave defrost via CAN bus
has not been configured correctly
Check parametrisation: Check the internal/
external defrost timer, defrost times, alarm
delay time, configuration of the master/
slave defrost via CAN bus(see chapter
), check the
configuration of the consecutive defrost via
CAN bus (see chapter
).
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...