5.7.2 Control of the expansion valves
The output of the opening degree for controlling the two electronic expansion valves of zone 1 and zone 2 is
provided at the factory via the pulsing (PWM - pulse width modulation) of the two semiconductor relays EEV1
and EEV2 and the two analogue outputs AO1 and AO2 (only UA 410 E AC).
UA 400 E CC / UA 410 E AC
UA 401 E CC
UA 400 E CC / UA 410 E AC
Single-zone operation
Single-zone operation
Two-zone operation
Standalone operation
EEV1
on terminals 23/24
EEV1 and EEV2
on terminals 23/24 and 33/34
Terminal assignment of the 230 V AC relay outputs
Pulsed electronic expansion valves
The parameter "
Freigaberel.
(menu 6-3)
must
be configured to "OFF" (factory setting) so that the
semiconductor relays output the opening degree in a
timed
way: