Firmware V3.13
21.04.2021
438/466
•
Menu 6-2-3 Alarm Delay
ALARMDELAY POS: XXXXX
Entry
Default
Sensor Fault XX m
Sensor break alarm delay
0..30
15 min
High/Low Temp. XX m
High/low temperature alarm delay
0..150
90 min
No Defrost XX h
No defrost alarm delay
--, 2..168
--- h
Selfholding N
Alarm latching with manual alarm cancelling (YES)
or automatic cancelling on send (NO)
↑, ↓,
(Y/N)
N