Firmware V3.13
21.04.2021
29/466
5.3 CAN bus mode
The controller is integrated in the CAN bus in this operating mode. The
generally performed via the system centre, which also takes care of the alarm management. In addition, the
suction gas temperature t
0
of the pack controller belonging to the refrigeration circuit via the CAN bus is used to
determine superheat.
For this operating mode, a correction offset fro the pressure losses in the suction line
must
be determined for
each
refrigeration point and set to "xx" using the parameter
Korroff. t
0
(menu 6-3). If the parameter
Korroff. t
0
is
set to "--", the controller is then in
•
•
ATTENTION
Compressor damage! Danger due to liquid refrigerant on the suction side of the compressor!
Operating mode
t
0
via CAN bus
(menu 6-2-6)
The evaporator inlet sensors R5.1 and R5.2 should also be connected in the
t
0
via CAN
bus
operating mode. This results in improved emergency running characteristics in the event of
failure of the CAN bus transmission. In standalone operation (without local pressure transmitter),
the sensors, R5.1 and R5.2
must
be connected; see chapter
Operating mode
t
0
local Z1 / Z2
(menu 6-2-6)
In the case of evaporators with high cooling capacity which require
high control dynamics
, the
superheat control should be realised via a local pressure transmitter (only UA 410 E AC); see
chapters
Standalone operation using activated local pressure transmitter
and
Superheat control only via sensors R5.1 and R5.2 is not recommended, as there is a risk of
evaporator flooding due to the slow response behaviour!
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...