Firmware V3.13
21.04.2021
226/466
•
Menu 6-7 COPT+
COPT+ POS: XXXXX
Entry
Default
COPT+ xxx
Principle participation of the controller in the suction
pressure shift. (function COPT+).
Note: This is transmitted via a CAN bus telegram
and intervenes in the regulation!
↑, ↓,
(ON/OFF)
AUS
Inact.a.Def xxm
Delay time following completion of the defrost before
the controller actively intervenes in the shift.
0..40
30 min
Dely_HystON xxxxm
Delay time for the reduction request with active
cooling and overshoot of the hysteresis.
0..10
2.5 min
HiTmpZ1 dwn xxm
Delay time before the elapse of the high temperature
alarm delay in zone 1, before the reduction is
requested.
0..15
5 min.
HiTmpZ2 dwn xxm
Delay time before the elapse of the high temperature
alarm delay in zone 2, before the reduction is
requested.
0..15
5 min.
TolOvHystZ1 xxK
Tolerance limit above the setpoint plus hysteresis in
zone 1. Influences when it is switched from stop to
reduce.
0..20
2 K
TolOvHystZ2 xxK
Tolerance limit above the setpoint plus hysteresis in
zone 2. Influences when it is switched from stop to
reduce.
0..20
2 K
SwtchSupRet xxx
Switching from supply air to return air and the
reverse
with temperature alarm delay time.
↑, ↓,
(ON/OFF)
AUS
Dely_Switch xxxm
Switching from supply to return air: determines when
it is switched within the delay time for the high
temperature alarm.
0..15
5 min.
Add.Values xxx
Creation of additional (additive) “Debug” actual value
archives in the system centre / store computer.
Warning:
This can force a reorganisation of the
actual
value archives – for this reason
only
use when
required!
↑, ↓,(EIN/AUS)
AUS
Incl_UpLim xxxK
Upper limit of the neutral zone for determining the
incline.
0..5
0.3 K
Incl_LwLim xxxK
Lower limit of the neutral zone for determining the
incline.
0..5
0.2 K
SDS Hyst Z 1 xxxK
Determines the hysteresis used during the shift from
this value and the P-quota Möbelreg. Zone 1. (*)
1..10
5 K
SDS Hyst Z 2 xxxK
Determines the hysteresis used during the shift from
this value and the P-quota Möbelreg. Zone 2. (*)
1..10
5 K
SDS RMode virtSet
Please always leave this value on
“virtSwt”
-
virtSwt
( * ) The lower this parameter, then the earlier the pack controller is instructed to lower the suction pressure,
which increases the accuracy with which the controller can maintain its setpoint. In addition the case controllers
P-quota is also employed. The higher the case controller’s P-quota, then the earlier the pack controller is
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...