EEV ZONE 1 POS: XXXXX
Entry
Default
inject.time XX.X m
Injection time following the switching on of the
controller or following a defrost or in the event of
a blockade of the regulation.
The value entered must not be greater than the
current ”
setuptime
” parameter, otherwise the
largest valid value will be used.
Further details about “Fixed valve opening degree
in pumpdown/feed-in phase” see chapter
valve opening degree in pumpdown/feed-in
phase
.
0..100.0
0.5 min
OD over CAN XXX
Send opening degree via CAN bus
(is employed when a demand dependent setpoint
evaluation / to shift via consumer” is
parameterised in the corresponding pack
controller)
↑, ↓,
(ON/OFF)
ON
15s Archiv X
A few statuses and values are additionally
archived at 15 second intervals in the system
centre / store computer when this parameter is
set to “J”.
WARNING: This setting increases the memory
requirement and should only be activated when
needed / for diagnostic purposes.
↑, ↓,
(Y/N)
N
OD 3s interv XXX
Select interval for output of opening degree.
OFF = 6s
ON = 3s
Control is suspended for 6 seconds when
toggling.
↑, ↓,
(ON/OFF)
OFF
Reset I-Sum XXX
Reset I-sum (to zero) if superheat drops below
set minimum for longer than time set by ”delay
min SH” parameter.
OFF = I-sum not reset to zero
ON = I-sum is reset to zero
↑, ↓,
(ON/OFF)
ON
edit op.deg. XXX
Manual entry of valve opening degree
↑, ↓,
(ON/OFF)
OFF
op.deg. Z 1 XXX %
Current valve opening degree Zone 1; can be
edited when manual entry is activated
0..100
Default by controller
Maximum OD xxx %
Sets an upper limit to the opening degree output
by the case controller
20..100
100%
Lo Temp to xxK
Monitoring of the t0 transmitted by the pack
controller for unsuitably low values
NOTE: Following commissioning this value can
be set to ”-”.
10..60, --
28K
to VS corr. XXX °C
Displays current corrected suction pressure
temperature on pack controller (assigned by Pack
No.)
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...