Firmware V3.13
21.04.2021
68/466
In two-zone operation, the sensors R1.1 and R1.2 are used for the defrosting.
R1.1: Defrost sensor (terminals Z31/Z32)
R1.2: Defrost sensor (terminals Z81/Z82)
E-valve 1: Relay for expansion valve 1 (terminals 23/24)
E-valve 2: Relay for expansion valve 2 (terminals 33/34)
Defrost heater 1: Relay for defrost heater 1 (terminals 43/44)
Defrost heater 2: Relay for defrost heater 2 (terminals 53/54)
Assignment of the sensors to the defrost relays
Optional not attached sensors are not used for switching the defrost relay.
Controller type
Sensor
Comment
UA 121 E, UA 131 E, UA 131 E LS, UA 141 E,
UR 141 NE, UR 141 TE, UK 100 E, KR 160 E
R1.1
Defrost relay 1
R1.2
Defrost relay 2