Firmware V3.13
21.04.2021
93/466
4. "Delay after the defrost" operating mode
The fan relay is switched on continuously during the cooling in this operating mode. The fan relay switches off
at the start of a defrost. The fan relay remains switched off during the defrost. When the defrost is finished, the
fan relay switches on again if the parameter
Lüfteranlauf
on the evaporator is undercut.
In single-zone operation, only the evaporator sensor R1.1 has to fall below the value of
Lüfteranlauf
so that the
fan relay is switched on.
In two-zone operation, both evaporator sensors R1.1
and
R1.2 must fall below the value of
Lüfteranlauf
so that
the fan relay is switched on again. If the evaporator sensor R1.2 is not attached, then the fan relay is also only
controlled via R1.1 in two-zone operation.
The fan relay is switched off during any possibly parametrised wait or drip time. The parameter
Lüfter
Über
has no effect in this operating mode.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...