Firmware V3.13
21.04.2021
220/466
EEV ZONE 1 POS: XXXXX
Entry
Default
OD over CAN XXX
Send opening degree via CAN bus (is employed
when a demand dependent setpoint evaluation / to
shift via consumer” is parameterised in the
corresponding pack controller)
↑, ↓, (ON/OFF)
AUS
15s Archiv X
A few statuses and values are additionally archived
at 15 second intervals in the system centre / store
computer when this parameter is set to “J”.
WARNING: This setting increases the memory
requirement and should only be activated when
needed / for diagnostic purposes.
↑, ↓, (Y/N)
N
OD 3s interv XXX
Select interval for output of opening degree.
OFF = 6s
ON = 3s
Control is suspended for 6 seconds when toggling.
↑, ↓,
(ON/OFF)
OFF
Reset I-Sum XXX
Reset I-sum (to zero) if superheat drops below set
minimum for longer than time set by ”delay min SH”
parameter.
OFF = I-sum not reset to zero
ON = I-sum is reset to zero
↑, ↓,
(ON/OFF)
ON
edit op.deg. XXX
Manual entry of valve opening degree
↑, ↓,
(ON/OFF)
OFF
op.deg. Z 1 XXX %
Current valve opening degree Zone 1; can be edited
when manual entry is activated
0..100
Default by
controller
Maximum OD xxx %
Sets an upper limit to the opening degree output by
the case controller
20..100
100%
Lo Temp to xxK
Monitoring of the t
0
transmitted by the pack
controller for unsuitably low values
NOTE: Following commissioning this value can be
set
to ”-”.
10..60, –
28K
to VS corr. XXX °C
Displays current corrected suction pressure
temperature on pack controller (assigned by Pack
No.)
—
—
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...