Firmware V3.13
21.04.2021
38/466
Only UA 410 E AC
Continuous motor expansion valves
T
he
opening degree is also output simultaneously via the two analogue outputs 0..10 V (corresponds to
0..100%) for the control of
continuous motor expansion valves
(factory setting):
The following
must
be observed when using the analogue outputs:
The opening degree at the two analogue outputs is
only
output if the coding switch
6
of the DIP switch
S3
is
also set to
OFF
(factory setting; for details, see chapter