Firmware V3.13
21.04.2021
91/466
2. Operating mode "fan flow"
The fan relay is switched on continuously during the cooling in this operating mode.
The fan relay switches off at the start of a defrost. The fan relay switches on if the parameter
Lüfter Über
at the
evaporator sensor is exceeded. When the defrost is complete, the fan relay Is switched on again in all cases.
Only the evaporator sensor R1.1 is used for fan control in single-zone operation.
Both evaporator sensors R1.1
and
R1.2 are used for fan control in two-zone operation. If the evaporator sensor
R1.2 is not attached, then only the evaporator sensor R1.1 is also used for fan control in two-zone operation.
The fan relay does not change its state during any possibly parametrised drip time. The
parameter
Lüfter Über
is already evaluated during a possibly parametrised wait time. The
parameter
Lüfteranlauf
has no effect in this operating mode.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...