Firmware V3.13
21.04.2021
77/466
•
•
5.8.5
Master/slave mode – defrost synchronisation via wiring
All controller types except UK 100 E or KR 160 E
Requirements
External 230 V AC wiring on hardware side
Setting of the DIP switch S3, coding switch 4
must
be set to
ON
; for details, see chapter
controller type and other functions
Function Description
The master/slave mode is used for refrigerated cases, for which the operation of multiple evaporators can result
in reciprocal icing of the evaporators without further protective measures.
This problem is prevented due to the defrost synchronisation in master/slave mode. All refrigerated cases and
case zones defrost simultaneously and then switch to cooling together. Multiple participating controllers are
synchronised via hardware wiring, see chapter
Wiring of the master-slave function for defrost synchronisation
In addition, in the case of
one
controller in two-zone operation, this can be used to force the joint return of both
zones to cooling following a defrost.
ATTENTION
Damage to the system and stock loss!
When using this function, it must be ensured that
incorrect
parametrisation
does not result in simultaneous defrost and cooling of the synchronised refrigeration
points.
DANGER
This function requires
additional external
wiring for multiple participating controllers. It must be
ensured for the wiring of master and slave case controllers that the power supply is only
implemented with
one phase
(e.g. only via L1)! For details, see chapter
function for defrost synchronisation.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...