Firmware V3.13
21.04.2021
125/466
Example:
S1
= 3 = 3 x 10 = 30 and
S2
= 4 = 4 x 1 = 4
→ CAN bus address = S1 + S2 = 30 + 4 =
34
6.2.2 Setting the controller type and other functions
Setting of the controller type
The required controller type can be set via the
DIP switch S3
by adjusting the coding switches 1..9 with a thin
screwdriver (D = 2 mm) through a hole in the case cover:
The case controller does not accept the settings on the decade switches
S1
and
S2
until after the
controller has been briefly disconnected from the power supply! In the case of case controllers that are
installed in a switch cabinet, the CAN bus address has been set by the manufacturer. However, it can
be subsequently adjusted.
DANGER
Warning about dangerous electrical voltage!
Danger of electric shock!
The DIP switch S3 may only be adjusted when
disconnected from the
power supply
. The changes are not applied until the next time the controller is switched on.
ATTENTION
Caution: data loss!
All parameters are reset to their factory settings if the controller type is changed or
due to a first start (see chapter
First start / reset controller to factory settings
)!
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...