Menu 2-2-2 Zone 2
DEFROST 2 POS: XXXXX
Entry
Default
Counting Rate X
Setpoint of time during which evaporator defrost
termination temperature may be within band around 0°C
before defrost counter counts down
0..15
0
Defrost Counter X
Setpoint of count for number of defrost cycles to be
skipped. By pressing the ¿ key the value can be set to 1
until it is automatically reset to the basic settings.
1
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
10 °C
Wait Time XX m
Waiting time setpoint between cooling and defrost
0..15
3 min
Drip Time X m
Waiting time (drip time) setpoint between defrost and
cooling
0..15
5 min
Menu 2-2-3 Zone 1T Toggle
DEFROST 1A POS: XXXXX
Entry
Default
Counting Rate X
Setpoint of time during which evaporator defrost
termination temperature may be within band around
0°C before defrost counter counts down
0..15
0
Defrost Counter X
Setpoint of count for number of defrost cycles to be
skipped. By pressing the ¿ key the value can be set to
1 until it is automatically reset to the basic settings.
1
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
10 °C
Wait Time XX m
Waiting time setpoint between cooling and defrost
0..15
3 min
Drip Time X m
Waiting time (drip time) setpoint between defrost and
cooling
0..15
5 min
2.Defrst Level XXX °C
2nd defrost stage setpoint; shown only when single-
zone operation is set (Menu 6-1)
--, -20..30
--
Menu 2-2-4 Zone 2T Toggle
DEFROST 2A POS: XXXXX
Entry
Default
Counting Rate X
Setpoint of time during which evaporator defrost
termination temperature may be within band around 0°C
before defrost counter counts down
0..15
0
Defrost Counter X
Setpoint of count for number of defrost cycles to be
skipped. By pressing the ¿ key the value can be set to 1
until it is automatically reset to the basic settings.
1
Def. End. Tmp. XX °C
Defrost termination temperature setpoint
--, 0..30
10 °C
Wait Time XX m
Waiting time setpoint between cooling and defrost
0..15
3 min
Drip Time X m
Waiting time (drip time) setpoint between defrost and
cooling
0..15
5 min
Menu 2-3 Fan
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...