Firmware V3.13
21.04.2021
372/466
ATTENTION
Damage to the system and stock loss!
It must be ensured that the correct pack number has been
selected, i.e. the correct Refr. Sys. type has been set, otherwise this can result in damage to the
installation or goods. Furthermore, the parameter
Corr.off t
0
(menu 6-3) must not be set to ”--” if the t
0
from the pack controller is to be used for regulating.
A meaningful name that describes the refrigeration point in more detail should be entered, e.g. Cheese
Counter 2 and CC2. Entry is made in the screens on system centre, store computer or operator
terminal. Direct entry cannot be made in the controller screens displayed on the operator terminal.
Entry cannot be made either on operator interface BT 300.