Firmware V3.13
21.04.2021
375/466
•
1.
2.
3.
4.
•
Menu 6-2-4 230V Inputs
230V INPUT POS: XXXXX
Entry
Default
Entry1: XXXXXXXXXX
Function of digital input 1 D11/D12
1)
DEFR.TIMER
Entry2: XXXXXXXXXX
Function of digital input 2 D21/D22
2)
TOGGLE SETP.
Entry3: XXXXXXXXXX
Function of digital input 3 D31/D32
3)
DOOR CONTACT
Entry4: XXXXXXXXXX
Function of digital input 4 D41/D42
4)
Extern.Alarm
XXXXXXXXXXXXXXXXXXX
Freely configurable alarm text for digital input
4,
the default text is “CO2-Alarm”
Text
CO2-ALARM
Inv. D1 XXX
Inverting of digital input 1
↑, ↓,
(ON/OFF)
OFF
Inv. D2 XXX
Inverting of digital input 2
OFF
Inv. D3 XXX
Inverting of digital input 3
OFF
Inv. D4 XXX
Inverting of digital input 4
OFF
Possible settings for the digital inputs:
DEFR.TIMER Defrost timer*
MANUAL OFF. Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP. Toggle setpoint
TOGGLE SETP Toggle setpoint *
DOOR CONTACT Door contact
MANUAL OFF Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
DOOR CONTACT Door contact *
MANUAL OFF Manual shutoff both zones *
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
EXT ALARM External Alarm *
MANUAL OFF Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP Toggle setpoint
* Factory setting
Menu 6-2-5 Sensor Type
Selection is made according to entry. Checkmark shows current setting.
ATTENTION
Damage to the system and stock loss!
Only trained personnel should be allowed to change digital
inputs, as chenges can affect other functions.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...