Firmware V3.13
21.04.2021
31/466
5.4.2 Standalone operation using activated local pressure transmitter
Only UA 410 E AC
If this operating mode is used, the suction gas temperature t
0
for determination of the superheat is calculated
using the suction gas temperature t
0
coming from the local pressure transmitter
and
the value of the evaporator
outlet sensor R6.x; see chapter
. This operating mode is recommended for evaporators with
high refrigerating capacity that require
high control dynamics
:
The determination of the superheat via the local pressure transmitter is activated by setting the parameter
AIn1
aktiv
to "ON" (menu 6-2-6). The suction gas temperature t
0
determined using the local pressure transmitters is
always the preferred one; even if the suction gas temperature t
0
transmitted by the pack controller via the CAN
bus is available in the controller, as the controller is integrated in the
ATTENTION
In the event of failure of the pressure transmitters
and
the CAN bus (suction gas temperature t
0
for
superheat control is no longer available), the controller can operate
to a limited extent
in the so-called
standalone mode. This means that the case controller operates autonomously. In this case, R5.x
and
R6.x are necessary sensors and
must
be connected; see chapter
.
Further parameters for the configuration of local pressure transmitters must be observed; for further
details, see chapter
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...