Output of fixed analogue values (coding switch 6 = ON)
The output of fixed analogue values (0..10 V) at the two analogue outputs for the control, e.g. of a fan speed
of 0..100%:
Analogue values of 0..100% (corresponds to 0..10 V) can be set for each zone in menu 2-1-1 and 2-1-2:
- Parameter
Kühl. ein AOUT
: cooling switched on; e.g. a high (maximum) fan speed is required during
cooling operation.
- Parameter
Kühl. aus AOUT
: cooling switched off; e.g. a low (minimum) fan speed is required.
5.13 Light control
The case controller is equipped for activating the case lighting / night blind. Activation is carried out via the
transistor output 1 (terminals 81/82, see chapter
Belegung der 24 V DC-Transistorausgänge
ATTENTION
If a fixed analogue value is required (coding switch 6 = ON), the parameter "
Freigaberel.
"
must
also be set to "OFF" so that the two expansion valves for cooling are controlled.
Failure of the cooling:
If the parameter "
Freigaberel.
" is set to "ON" (for details, see chapter
Enable relay for motor expansion valves
)
and
the coding switch 6 = ON, then there is
no
possibility
for control of the expansion valves!
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Страница 207: ...Firmware V3 13 21 04 2021 207 466...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C...
Страница 277: ...Firmware V3 13 21 04 2021 277 466...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm...