No.
Message text
Cause
Remedy
Messages
143
OD manual zone 1
The control function has been disabled. The
opening degree is set manually.
–
OD manual zone 2
144
Config.: M/S mit DG
Master-Slave mode and hotgas defrosting
have been activated simultaneously.
Check configuration
179
CO2-Alarm
External alarm (specified as CO2-Alarm in
the default settings)
–
189
Refrigeration point disabled
Block of the compressor enable.
–
240
Setpoint changed
A setpoint has been adjusted.
–
In the Master-Slave mode, the defrost
relays are only switched off via
temperature or safe defrost time. In
contrast, during hotgas defrosting, the
relays are also switched off via the CAN
bus even if the pack controller defrost
command does not occur. These two
requirements are incompatible.