SiUS342303E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
156
Note(s)
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however cannot
be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the
indoor unit is not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote
controller is resetting when returning to the normal mode.
13 (23)
0
Setting of airflow rate
Standard
High ceiling 1
High ceiling 2
—
1
Airflow direction setting
4-direction
airflow
3-direction airflow
2-direction
airflow
—
2
Swing pattern settings
All direction
synchronized
swing
—
Facing
swing
—
4
Setting of airflow direction
adjustment range
Draft prevention
Standard
Ceiling soiling
prevention
—
5
Setting of static pressure
selection
Standard
High static
pressure
—
—
6
External static pressure
settings
Refer to page on the right for details.
14 (24)
4
Optional kit setting (UV lamp
+ humi economizer)
Refer to page on the right for details.
5
Dry mode set temperature
Room
temperature
Same as cooling
mode set
temperature
—
—
9
Mold proof operation setting
—
Standard
For high
humidity areas
—
11
Gas furnace test mode
OFF
Low heat
High heat
—
15 (25)
0
Drain pump operation setting
—
ON
OFF
—
1
Humidification when heating
thermostat is OFF
Not equipped
Equipped
—
—
2
Setting of direct duct
connection
Not equipped
Equipped
—
—
3
Interlocked operation
between humidifier and drain
pump
Not
interlocked
Interlocked
—
—
5
Individual setting of
ventilation
Normal
Individual
—
—
1b
4
Display of error codes on the
remote controller
—
Two-digit display
—
Four-digit
display
1c
0
Room temperature display
Not displayed
Displayed
—
—
1
Thermistor sensor for auto
changeover and setback
control by the remote
controller
Utilize the return
air thermistor
Utilize the
remote
controller
thermistor
—
—
3
Access permission level
setting
Level 2
Level 3
—
—
10-15 Remote controller thermostat
offset
Refer to page on the right for details.
1e
2
Setback availability
N/A
Heat only
Cool only
Cool/heat
14
Setting "restricted / permitted"
of airflow block
Refer to page on the right for details.
Mode
No.
(Note 2)
First
Code
No.
Setting Contents
Second Code No.
Reference
Page
01
02
03
04
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...