Field Settings for Indoor Unit
SiUS342303E
175
Part 5 Field Settings and Test Operation
1.4.30 Mold Proof Operation Setting (for FXEQ-P models)
Areas with average humidity over 80%.
1.4.31 Gas Furnace Test Mode (for CXTQ-TA models)
This setting is used for gas furnace test run.
For details, refer to
Gas Furnace Test Operation
on page 222.
1.4.32 Drain Pump Operation Settings (for FXMQ-PB models)
The drain pump operation can be disabled for natural drainage by changing the following field
setting.
: Factory setting
1.4.33 Humidification when Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 20°C (68°F)
or above and turns OFF the humidifier if suction air temperature is 18°C (64.4°F) or below when the
heating thermostat is OFF.
: Factory setting
1.4.34 Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. If the second code is set to
02: Equipped, energy recovery ventilator fan conducts the fan residual operation by linking to
indoor unit. The indoor fan carries out residual operation for one minute after the thermostat is
stopped. (For the purpose of preventing dust on the air filter from falling off.)
: Factory setting
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
14 (24)
9
01
—
02
Standard
03
For high humidity areas (
)
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
14 (24)
11
01
OFF
02
Low heat
03
High heat
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
0
01
—
02
ON
03
OFF
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
1
01
Not equipped
02
Equipped
Mode
No.
First Code
No.
Second Code
No.
Contents
15 (25)
2
01
Not equipped
02
Equipped
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...