SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
340
Note(s)
Reference
Reference
3.58 Refrigerant Shortage
Applicable
Models
All outdoor unit models
Error Code
U0
Method of Error
Detection
Detect refrigerant shortage according to a low pressure level or a difference in heat exchanging
temperature from the suction pipe.
Error Decision
Conditions
Low pressure becomes 0.1 MPa (14.5 psi) or less.
Error is not determined. The unit continues the operation.
Supposed
Causes
Refrigerant shortage or refrigerant clogging (wrong piping)
Defective thermistor
Defective low pressure sensor
Defective outdoor unit main PCB
Troubleshooting
CHECK 2
Refer to page 372.
CHECK 12
Refer to page 384.
Is the low
press
u
re 0.1 MPa
(14.5 psi) or less?
(
∗
1)
Is the
characteristics of
low press
u
re sensor
normal? (
∗
2)
Replace the low press
u
re
sensor (S1NPL).
Replace the o
u
tdoor
u
nit
main PCB (A1P).
NO
NO
YES
YES
Eliminate factors that ca
u
se
decreasing low press
u
re.
CHECK 2
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
(1) Mo
u
nt a press
u
re ga
u
ge at the ser
v
ice port on the low
press
u
re side.
(2) Reset the operation
u
sing the remote controller then
restart.
1. Check the low pressure value by using pressure gauge in operation.
2. Compare the actual measurement value by pressure sensor with the value by the
pressure gauge.
(To gain actual measurement value by pressure sensor, measure the voltage at the
connector [between (2)-(3)] and then convert the value into pressure.
CHECK 12
)
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...