SiUS342303E
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
192
47
Heat pump
lockout release
differential
Heat pump would be resumed
when the outdoor air temperature
is recovered by differential above
the heat pump lockout
temperature.
2.
4
7
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
0
1
2
49
Outdoor > 50 m
(164 ft) above
indoor
Height difference setting max. 110
m (361 ft).
2.
4
9
Off (max. 50 m (164 ft))
On (max 110 m (361 ft))
0
1
50
Auxiliary heater
maximum
allowable
temperature
Auxiliary heater is allowed to
energize when the ambient
temperature is smaller than the
auxiliary heater maximum
allowable temperature.
2.
5
0
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
12.7°C (55°F)
15.5°C (60°F)
18.3°C (65°F)
Auxiliary heater always not
allowed
Auxiliary heater always
allowed
1
1
1
1
1
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
51
Sequence multi
outdoor
Sequence addressing between
master and sub units.
2.
5
1
Automatic
Forced master
Forced sub
0
1
2
52
Auxiliary heater
maximum
allowable
temperature
release
differential
Auxiliary heater is not allowed to
energize when the outdoor air
temperature is recovered by
differential above the auxiliary
heater maximum allowable
temperature.
2.
5
2
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
0
1
2
62
Cooling/Heating
capacity learning
control
Adjust cooling and heating capacity
learning control
2.
6
2
OFF
Cooling adjustment
Heating adjustment
Cooling and heating
adjustment
0
1
2
3
65
Heat pump
lockout
temperature
Heat pump is locked out when the
outdoor air temperature is smaller
than the heat pump lockout
temperature.
2.
6
5
–26.1°C (–15°F)
–23.3°C (–10°F)
–20.5°C (–5°F)
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
Forced heat pump lockout
1
1
1
1
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
76
VRTsmart
control
Te upper limit
Used to change upper limit of
target evaporation temperature in
VRTsmart control.
2.
7
6
Low 1
Low 2
Low 3
Low 4
Low 5
Low 6
Standard
High
0
1
2
3
4
5
6
7
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...