SiUS342303E
Protection Control
Part 4 Functions and Control
112
6.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient decrease
of low pressure.
Cooling
Because of common low pressure, the following control is performed in the system.
Heating
The following control is performed in the system.
6.3 Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
HTdi: Value of compressor discharge pipe temperature (Tdi) compensated with outdoor air
temperature
Ti: Compressor body temperature
A: Maximum of HTdi and Ti
The following control is performed for each compressor of single unit as well as multi units.
Normal control
Low pressure standby
Reduce compressor capacity step
When occurring 3 times within 60
minutes, the error code
E4
is output.
Pe: Low pressure sensor detection
value for master unit.
Pe < 0.25 MPa
(36.3 psi)
Pe > 0.39 MPa
(56.6 psi)
Pe < 0.07 MPa
(10.2 psi)
Normal control
Low pressure standby
Reduce compressor capacity step
When occurring 3 times within 60
minutes, the error code
E4
is output.
Pe < 0.05 MPa
(7.3 psi)
Pe > 0.1 MPa
(14.5 psi)
Pe < 0.02 MPa
(2.9 psi)
Normal control
HTdi > 135°C
(275°F)
A > 108°C
(226°F)
Reduce compressor capacity step
Discharge pipe temperature standby
When occurring 3 times within 100
minutes, the error code
F3
is output.
(Sub code - 01, 02, 03)
A < 95°C
(203°F)
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...