Troubleshooting by Error Code
SiUS342303E
337
Part 6 Service Diagnosis
3.56 Inverter Radiation Fin Temperature Abnormality
3.56.1 Inverter Radiation Fin Temperature Abnormality (Inverter PCB)
Applicable
Models
All outdoor unit models
Error Code
P4
Sub code: 09-13
Method of Error
Detection
Detect the resistance of the following thermistors while the compressor is not running:
Radiation fin thermistor
Thermistor located in PCB circuit
Heat sink thermistor
Error Decision
Conditions
When the resistance of the thermistor comes to a value equivalent to open or short circuit.
Error is not decided while the unit operation is continued.
P4
will be displayed by pressing the inspection button.
Supposed
Causes
Defective radiation fin temperature thermistor
Defective inverter PCB
Defective compressor
Defective fan motor
Troubleshooting
Make measurement of
resistance of the radiation fin
thermistor.
Is the
resistance of the
relevant thermistor
normal?
The
insulation
resistance of the
relevant compressor is not
more than 100 k
.
The insulation
resistance of the relevant
fan motor is not more
than 1 M
.
Turn ON
the power supply.
Does the error
recur?
NO
YES
NO
YES
NO
YES
YES
NO
Replace the inverter PCB.
Replace the compressor.
Replace the fan motor
(M1F, M2F).
Replace the inverter PCB.
Continue operation.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...