Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
194
2.4.3 Details of Setting Mode 2
Mode 2 is used to change the field settings of the system. Consulting the current field setting value
and changing the current field setting value is possible.
In general, normal operation can be resumed without special intervention after changing field
settings.
Some field settings are used for special operation (e.g. 1 time operation, recovery/vacuuming
setting, adding refrigerant setting, etc.). In such a case, it is required to abort the special operation
before normal operation can restart. It will be displayed in below explanations.
[2-0]:
Cool/Heat selection setting
Cool/Heat selection setting is used in case the optional Cool/Heat selector
(KRC19-26A) is used. Depending on the outdoor unit setup (single outdoor unit setup or
multi outdoor unit setup), the correct setting should be chosen. More details on how to
use the Cool/Heat selector option can be found in the manual of the Cool/Heat selector.
Default value: 0.
0: Each individual outdoor unit can select Cool/Heat operation (by Cool/Heat selector
if installed).
1: Master unit decides Cool/Heat operation when outdoor units are connected in
multiple system combination
2: Sub unit for Cool/Heat operation when outdoor units are connected in multiple
system combination
Change [2-0] to 0, 1 or 2 in function of required functionality.
[2-1]:
Cool/Heat unified address
Address for cool/heat unified operation.
When multiple heat pump systems need to change over together between cooling
and heating (example multiple systems serve indoor units in landscape area). Per
zone the optional PCB DTA104A62 needs to be installed. Recommended location is
in one of the
VRV
indoor units belonging to the system that will be set as “Master
cool/heat unit” (field setting 2-0-1).
The address set to the multiple systems need to operate as a zone, should be
same as the address set by the DIP switches on the related optional PCB
DTA104A62.
External
control adaptor
for outdoor unit
No.0
Outdoor
unit group
master No.0
Outdoor
unit group
sub No.0
Outdoor
unit group
sub No.0
Outdoor
unit group
master No.2
Outdoor
unit group
sub No.2
Outdoor
unit group
sub No.2
Outdoor
unit group
master No.1
Outdoor
unit group
sub No.1
Outdoor
unit group
master No.3
Outdoor
unit group
sub No.3
External
control adaptor
for outdoor unit
No.1
External
control adaptor
for outdoor unit
No.2
External
control adaptor
for outdoor unit
No.3
DS2, DS1
DS2, DS1
DS2, DS1
DS2, DS1
C/H group address
C/H group address
C/H group address
C/H group address
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...