Outline of Control (Indoor Unit)
SiUS342303E
147
Part 4 Functions and Control
Note(s)
9.16.3 Economizer
When indoor and outdoor air temperatures are reversed, the compressor is stopped to let in the
outdoor air to save energy.
This operation is called economizer operation, and the equipment to detect indoor and outdoor air
temperatures and open and close the damper to perform this operation is called an economizer.
The economizer detects indoor and outdoor air temperatures, informs the air conditioner that the
economizer operation is ready, and opens and closes the damper.
The indoor unit stops the outdoor unit when it receives a signal from the economizer and performs
air supply operation.
When the indoor air temperature is cooled down sufficiently by the economizer operation, and it is
no longer necessary (thermostat OFF), the indoor unit outputs a signal to the economizer to close
the damper.
&
Other conditions
Stop the thermostat ON signal (
∗
1)
to the economizer.
Transfer the thermostat ON signal (
∗
1) to
the economizer.
•
Cooling mode
•
When the thermostat is ON
Thermostat ON signal
&
Cooling mode
When the thermostat is ON
External output: ON (
2)
OR
Tcon
≤
Ts’ continues for 1
minute
Economizer set time (
3):
Free cooling only
&
Economizer set time (
3)
≠
Free cooling only
Thermostat ON continues for
the economizer set time (
3)
Air conditioner operation is
stopped.
The remote controller indicates
cooling operation.
The fan tap follows the remote
controller.
Air conditioner operation is
started.
The remote controller
indicates cooling operation.
The fan tap follows the
remote controller.
Normal operation
Other
conditions
Free cooling
Free cooling & Mech Cooling
Operation
Remote control ON
Remote control OFF
Stop indoor
u
nit ON signal (
∗
4)
to the economizer.
Transfer indoor
u
nit ON signal (
∗
4) to the
economizer.
Indoor unit ON signal
1. Thermostat ON signal: A signal to turn ON the indoor unit thermostat and allow the
economizer to open the damper.
It turns ON the relay on the X2M-ECONOMIZER2 on the PCB.
2. External input ON is an input signal to the X1M-ECONOMIZER1 terminal on the PCB.
3. Refer to
Optional Kit Setting (UV lamp + Humi Economizer) (for FXTQ-TA and
CXTQ-TA models)
4. Remote control ON signal: Contact output which shows the operating status of the indoor
unit.
This signal turns on the relay X2M-CONTROL ON/OFF on the PCB.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...