SiUS342303E
Outline of Control (Indoor Unit)
Part 4 Functions and Control
128
Assuming suction temperature has changed from 30°C (86°F) to 18°C (64°F) (F
A):
Suction air thermistor is used for temperatures from 30
C (86
F) to 25
C (77
F) (F
D).
Remote controller thermistor is used for temperatures from 25
C (77
F) to 21
C (70
F) (D
B).
Suction air thermistor is used for temperatures from 21
C (70
F) to 18
C (64
F) (B
A).
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near
the floor where the occupants are. When controlling by suction air thermistor only, the indoor unit
may therefore be turned off by the thermostat before the lower part of the room reaches the set
temperature. The temperature can be controlled so the lower part of the room where the occupants
are does not become cold by widening the range in which remote controller thermistor can be used
so that suction temperature is higher than the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 28°C (82°F) (A
D):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat sensor is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 25°C (77°F) (A
C).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 28°C (82°F) (C
D).
Assuming suction temperature has changed from 28°C (82°F) to 18°C (64°F) (D
A):
Remote controller thermistor is used for temperatures from 28°C (82°F) to 23°C (73°F) (D
B).
Suction air thermistor is used for temperatures from 23°C (73°F) to 18°C (64°F) (B
A).
Range in
w
hich remote controller
thermistor can be used
Range in
w
hich
suction air thermistor
can be used
Differential
Suction air temperature (TH1)
Set temperature (Ts)
12
14
16
1
8
20
22
24
26
2
8
30
32
34
53.6
57.2
60.
8
64.4
6
8
.0
71.6
75.2
7
8
.
8
8
2.4
8
6.0
8
9.6
93.2
°
C
°
F
°
C
32
30
2
8
26
24
22
20
1
8
16
°
F
8
9.6
8
6.0
8
2.4
7
8
.
8
75.2
71.6
6
8
.0
64.4
60.
8
TH1 = Ts + 12
≤
33
°
C
TH1 = Ts + 21.6
≤
91.4
°
F
TH1 = Ts + 10
≤
31
°
C
TH1 = Ts + 1
8
≤
8
7.
8
°
F
TH1 = Ts + 1
≤
31
°
C
TH1 = Ts + 1.
8
≤
8
7.
8
°
F
TH1 = Ts – 1
°
C
TH1 = Ts – 1.
8
°
F
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...