Field Setting from Outdoor Unit
SiUS342303E
187
Part 5 Field Settings and Test Operation
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
Changing and access the setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds), you can select
the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
To quit and return to the initial status, press the
MODE (BS1)
button.
Changing the value of the selected setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds) you can
select the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
Now the
SET (BS2)
button is used to select the required value of the selected setting.
When the required value is selected, you can define the change of value by pressing the
RETURN (BS3)
button once.
Press the
RETURN (BS3)
button again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor
unit’s fan).
Mode: 2
Setting: 18
Make sure the segment indication is as during normal operation (default situation when shipped
from factory).
Press the
MODE (BS1)
button for over 5 seconds; result segment display:
Press the
SET (BS2)
button 18 times; result segment display:
Press the
RETURN (BS3)
button once; the value which is returned (depending on the actual
field situation), is the status of the setting. In the case of [2-18], default value is "0", which
means the function is not active.
Result: mode 2 setting 18 is addressed and selected, return value is the current setting situation.
To change the value of the setting, press the
SET (BS2)
button until the required value appears
on the segment indication. When achieved, define the setting value by pressing the
RETURN
(BS3)
button once. To start operation according to the chosen setting, confirm again by
pressing the
RETURN (BS3)
button.
To leave the field setting, press the
MODE (BS1)
button once, you will return to the default
situation when shipped from factory.
Result: mode 2 accessed.
Result: mode 2 setting 18 is addressed.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...