SiUS342303E
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
196
Change [2-8] to 0, 2-7 in function of required operation method during cooling.
For more information and advice about the effect of these settings, refer to
Energy Saving and
Optimum Operation
[2-9]:
Tc target temperature during heating operation
Default value: 6
Value
[2-9]
Tc target
0
Auto
1
41°C (106°F)
3
43°C (109°F)
6 (default)
46°C (115°F)
Change [2-9] to 0, 1, 3 or 6 in function of required operation method during heating.
For more information and advice about the effect of these settings, refer to
Energy Saving and
Optimum Operation
[2-11]:
Eco level setting for Eco mode via External control adaptor.
Eco mode can be activated by short circuit the terminal on External control adaptor
(Optional) according to [2-11] setting. ([2-23] should be
0
)
This unit can operate with Te/Tc fix control and Eco mode. Eco mode means VRT
control.
If the terminal on external control adapter is not connected by short circuit with [2-11]
≠
0, the system operates according to [2-8] or [2-9] setting.
Default value: 0
Value
[2-11]
Meaning
Level
0 (default)
Inactive
—
1
Eco mode active by low noise
terminal short-circuit
Standard
2
Eco mode activate by demand
terminal short-circuit
2-C short circuit: Low
3-C short circuit: Standard
[2-12]:
Enable the night-time low noise function and/or power consumption limitation via
external control adaptor (DTA104A62)
If the system needs to run under night-time low noise operation or under power
consumption limitation conditions when an external signal is sent to the unit, this
setting should be changed. This setting will only be effective when the optional
external control adaptor (DTA104A62) is installed.
Default value: 0
To activate this function, change [2-12] to 1.
[2-13]:
AIRNET address
When an AIRNET system will be used, outdoor unit needs an AIRNET address.
Also to facilitate the recognition of a system in the map lay out of the service checker
type III, set each system a unique address between 1 and 63.
When duplicating of AIRNET address,
UC
error code will appear on central control.
[2-18]:
Fan high static pressure setting
In order to increase the static pressure the outdoor fan is delivering, this setting
should be activated. For details about this setting, see technical specifications.
Default value: 0
To activate this function, change [2-18] to 1.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...