Service Settings Menu, Maintenance Menu
SiUS342303E
95
Part 3 Remote Controller
Error Display
Display error ON
Displays the error on the screen.
Display error OFF
Displays neither errors nor warnings.
Display warning ON
Displays a warning on the screen if an error occurs.
Display warning OFF
No warning is displayed.
Swap Unit No.
Current Unit No.
A unit No. can be transferred to another.
Transfer Unit No.
Addressed Sensor
Value
Unit No.: 0 - 15
Select the unit number you want to check.
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
30: (
4)
31: (
4)(
5)
32: (
4)(
5)
33: (
4)
34: (
4)(
5)
35: (
4)(
6)
Remote controller thermistor (°C)
Suction air thermistor (°C)
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas pipe thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
Branch Selector unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Displays thermostat step 1 ON/OFF.
Thermostat step 1 OFF: 00
Thermostat step 1 ON: 01
Displays the heat demand that CXTQ-TA is currently
sending to the gas furnace (%).
Displays the fan demand that CXTQ-TA is currently
sending to the gas furnace (%).
Current status of heat pump ON/OFF for CXTQ-TA
HP OFF: 00
HP ON: 01
Current status of gas combustion heating
Displays current heat actual status (%).
Current airflow of the fan
Displays current airflow (CFM).
Data
The corresponding data will be displayed, based on
the unit number and Code selected.
1
(For FXTQ-TA, CXTQ-TA models)
The actual fan speed is converted into the fan tap to be displayed. Therefore, if the fan speed
is changed by controls or external factors, the airflow rate set with the remote controller may
differ from the fan tap display.
2
(For FXTQ-TA models)
0 rpm
is displayed even if the fan is rotating.
(For CXTQ-TA models)
- rpm
is displayed even if the fan is rotating.
3
(For FXTQ-TA, CXTQ-TA models)
The ON/OFF status of the humidifier connected to HUMIDIFIER on the X1M terminal of the
indoor unit PCB is not displayed. The ON/OFF status of the humidifier connected to the
wiring adaptor is displayed.
4
Only for CXTQ-TA
5
Displays
99
when it is more than 100%.
6
Display unit is by 100 CFM.
(ex. Displays
19
for 1850 CFM. Displays
18
for 1849 CFM.)
Maintenance Menu
Item 2
Remarks
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...