SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
304
Reference
Reference
3.36 Activation of Low Pressure Sensor
Applicable
Models
All outdoor unit models
Error Code
E4
Method of Error
Detection
Make judgment of pressure detected by the low pressure sensor with the outdoor unit main PCB.
Error Decision
Conditions
When low pressure caused a drop while the compressor is in operation:
Operating pressure: 0.07 MPa (10.2 psi)
Supposed
Causes
Abnormal drop in low pressure
Defective low pressure sensor
Defective outdoor unit main PCB
The stop valve is not opened
Troubleshooting
CHECK 2
Refer to page 372.
CHECK 12
Refer to page 384.
YES
NO
(1) Mount a pressure gauge on the low pressure service port.
(2) Reset the operation using the remote controller, and then restart the operation.
Is the stop valve open?
Open the stop valve.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor unit
main PCB (A1P).
NO
YES
Are both
pressure values the
same?
-The low pressure sensor is normal, and outdoor unit main PCB is also
normal.
-The low pressure has really become low.
CHECK 2
: Eliminate factors that cause the low pressure to fall.
Connect the service checker, and then compare the low pressure value
measured by the service checker with the voltage measurement of the
connector of the pressure sensor (
1)
Service Checker
CHECK 12
Replace the low pressure sensor
(S1NPL).
NO
Compare the voltage
measurement of the connector of the
pressure sensor (
1) with the measurement
of the pressure gauge. Are the
characteristics of the low
pressure sensor
normal?
CHECK 12
YES
(
1)
Use the table on
CHECK 12
to
convert the voltage measurement into
pressure measurement.
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...