Outline of Control (Indoor Unit)
Part 4 Functions and Control
140
Note(s)
9.11 Heater Control (Except FXTQ-TA Models)
Optional PCB KRP1B... is required.
The heater control is conducted in the following manner.
Normal control
While in heating, the heater control (ON/OFF) is conducted as shown below.
Overload control
When the system is overloaded in heating, the heater will be turned OFF in the following 2
manners.
1. The heater control (ON/OFF) is conducted through the liquid pipe temperature (R2T) of the
indoor unit.
2. The heater control (ON/OFF) is conducted by converting the heater temperature into the
condensing pressure equivalent saturated temperature (Tc) according to the temperature
detection through the high pressure sensor (S1NPH) of the outdoor unit.
Fan residual
operation
While the heater turns OFF, in order to prevent the activation of the thermal protector, the fan
conducts residual operation for a given period of time after the heater turns OFF. (This operation is
conducted regardless of with or without heater equipped.)
Residual operation time: 100 seconds on ceiling suspended type or 60 seconds on other types
O
N
Set temperature
OFF
2˚C
(3.6˚F)
2˚C
(3.6˚F)
O
N
43˚C (109.4˚F)
OFF
50˚C (122˚F)
Liquid pipe temperature
O
N
50˚C (122˚F)
60˚C (140˚F)
OFF
Condensing pressure
equivalent saturated
temperature
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...