Troubleshooting by Error Code
SiUS342303E
243
Part 6 Service Diagnosis
U1 - 01
Reverse phase/open phase of power supply (Master)
Refer to the
U1
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
U1 - 04
Reverse phase/open phase of power supply
(when power ON) (Master)
U1 - 05
Reverse phase/open phase of power supply (Sub)
U1 - 06
Reverse phase/open phase of power supply
(when power ON) (Sub)
U1 - 19
Power supply frequency issue (Master)
U1 - 20
Power supply frequency issue (Sub)
U2 - 01
Shortage of inverter 1 power supply voltage (Master)
Make a diagnosis of the relevant unit based on the
following.
Shortage of power supply voltage
If the other units detect shortage of power supply voltage,
power supply voltage during operation may be unstable.
Check the power supply condition.
If a particular unit detects the error, operation of 52C may
be defective. Follow the
U2
flowchart.
Open phase of power supply
The wiring between power supply and inverter PCB may be
disconnected. Check that power supply is connected to
terminal block, terminal block is connected to PCB without
broken wire or disconnection, and reactor wiring is
secured. If no abnormality is found, follow the
U2
flowchart.
Defective capacitor in main circuit
P-N on the inverter PCB (electrolytic capacitor, power
module) may be damaged and short circuited. Operation of
current limiting relay may be defective or the wiring
between the reactor and PCB may be disconnected.
Measure the resistance between P-N on the inverter PCB
and check for short circuit. If no abnormality is found, follow
the
U2
flowchart.
U2 - 02
Open phase of inverter 1 power supply (Master)
U2 - 03
Defective capacitor in inverter 1 main circuit (Master)
U2 - 08
Shortage of inverter 1 power supply voltage (Sub)
U2 - 09
Open phase of inverter 1 power supply (Sub)
U2 - 10
Defective capacitor in inverter 1 main circuit (Sub)
U2 - 22
Shortage of inverter 2 power supply voltage (Master)
U2 - 23
Open phase of inverter 2 power supply (Master)
U2 - 24
Defective capacitor in inverter 2 main circuit (Master)
U2 - 25
Shortage of inverter 2 power supply voltage (Sub)
U2 - 26
Open phase of inverter 2 power supply (Sub)
U2 - 27
Defective capacitor in inverter 2 main circuit (Sub)
U2 - 36
Fan motor 1 undervoltage (Master)
U2 - 37
Fan motor 1 undervoltage (Sub)
U2 - 39
Fan motor 2 undervoltage (Master)
U2 - 40
Fan motor 2 undervoltage (Sub)
U3 - 02
Initial installation warning
Refer to the
U3
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
U3 - 03
Test operation not conducted
U3 - 04
Abnormal end of test operation
U3 - 05
Premature end of test operation during initial transmission
error
U3 - 06
Premature end of test operation during normal
transmission error
U3 - 07
Premature end of test operation due to transmission error
of either unit
U3 - 08
Premature end of test operation due to transmission error
of all units
U4 - 01
Transmission error between indoor units and outdoor units Refer to the
U4
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
U4 - 03
Transmission error between indoor unit and system
U7 - 01
Error when external control adaptor for outdoor unit is
installed
Refer to the
U7
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
U7 - 02
Warning when external control adaptor for outdoor unit is
installed
U7 - 03
Transmission error between Master and Sub units
U7 - 05
Multi system error
U7 - 06
Error in address settings of Sub unit
U7 - 07
Connection of four or more outdoor units in the same
system
U7 - 11
Error in indoor unit connection capacity for test operation
U9 - 01
Other indoor units abnormality
Refer to the
U9
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
Error code
Troubleshooting
Error Description
Diagnosis
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...