Check
SiUS342303E
393
Part 6 Service Diagnosis
Warning
Warning
Electrical Checks - High Voltage Power Circuits
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
Line Voltage now present.
8.
The green LED on the diagnostic tool will blink indicating communications between the
tool and motor. See table below for indications of tool indicators and motor actions.
Replace or repair as needed.
Power
Button
Green
LED
Motor
Action
Indication(s)
OFF
OFF
Not
Rotating
Confirm 24VAC to UltraCheck-EZ
TM
tool. If 24VAC
is confirmed, diagnostic tool is inoperable.
ON
Blinking
Rotating
Motor and control/end bell are functioning properly.
ON
OFF
Rotating
Replace motor control/end bell.
ON
Blinking
Not
Rotating
Check motor (refer to Motor Checks on page 395).
ON
OFF
Not
Rotating
Replace motor control/end bell; verify motor (refer to
Motor Checks on page 395).
9.
Depress the orange power button to turn off motor.
10. Disconnect power. Disconnect diagnostic tool.
11. Reconnect the 4-wire harness from control board to motor.
1.
Disconnect power to air handler or modular blower.
2.
Disconnect the 5-circuit power connector to the ECM motor.
3.
Turn on power to air handler or modular.
4.
Measure voltage between pins 4 and 5 on the 5-circuit connector. Measured voltage
should be the same as the supply voltage to the air handler or modular.
5.
Measure voltage between pins 4 and 3. Voltage should be approximately half of the
voltage measured in step 4.
6.
Measure voltage between pins 5 and 3. Voltage should be approximately half of the
voltage measured in step 4.
7.
If no voltage is present, check supply voltage to air handler or modular blower.
8.
Disconnect power to air handler or modular blower. Reconnect the 5-circuit power
harness disconnected in step 2.
1
2
3
4
5
Lines 1 and 2 will be connected
for 120VAC Power Connector
applications only
Gnd
AC Line Connection
AC Line Connection
}
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...