Other Control
Part 4 Functions and Control
120
8. Other Control
8.1 Backup
Operation
If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor unit
from operating, and then conduct emergency operation only with operational compressors or
outdoor units.
"Emergency operation with remote controller reset" and "Emergency operation with outdoor unit
PCB setting" are available.
(1) Emergency operation with remote controller reset
[Operating method]
Reset the remote controller. (Press the
ON/OFF
button for 4 seconds or more.)
[Details of operation]
Disable the defective outdoor unit from operating temporarily, and then only operate other outdoor
units.
(On the system with 1 outdoor unit, this emergency operation is not available.)
(2) Emergency operation with outdoor unit PCB setting
[Setting method]
Make setting of the unit, "the operation of which is to be disabled", in field setting mode (setting
mode 2).
[Details of operation]
Disable the defective outdoor unit from operating, and then only operate other outdoor units.
(On the system with 1 outdoor unit, this emergency operation is not available.)
8.2 Heating
Operation
Prohibition
When outdoor air temperature is too high, outdoor unit cannot operate in heating mode
because:
Low pressure sensor can give pressure value above upper limit of sensor: error
JC
.
Mechanical internal load on compressor increases.
Low compression ratio can result in insufficient compressor internal oil lubrication.
Heating is disabled when outdoor air temperature is above 26°C (78.8°F).
Forced thermostat-OFF on indoor units.
Outdoor fan operates
≥
200 rpm.
Heating operation is enabled when outdoor air temperature drops below 24°C (75.2°F).
Содержание VRV EMERION RXYQ-AATJA
Страница 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Страница 380: ...Check SiUS342303E 373 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 379 CHECK 8 Refer to page 380...
Страница 405: ...SiUS342303E Wiring Diagrams Part 7 Appendix 398 RXYQ72 96 120 144 168 192 216 240AAYDA C 2D140769B...
Страница 406: ...Wiring Diagrams SiUS342303E 399 Part 7 Appendix 1 2 Indoor Unit FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 407: ...SiUS342303E Wiring Diagrams Part 7 Appendix 400 BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ TVJU 3D076375A...
Страница 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 413: ...SiUS342303E Wiring Diagrams Part 7 Appendix 406 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Страница 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 423: ...SiUS342303E Wiring Diagrams Part 7 Appendix 416 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269D...
Страница 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...